# PEWDB - Psychrometric Chart

**Location:** Refrigeration & Air Conditioning > Psychrometrics & Load Calculations > Psychrometric Chart

This module contains the approved instructional material in `PEWDB_Psychrometric_Chart_Guide.pdf` and is intended for integration into the PEWDB website/Python/Excel knowledge base.

## Required module sections
1. What a psychrometric chart represents
2. Select the correct chart / pressure / altitude
3. Dry-bulb temperature, wet-bulb temperature, humidity ratio, relative humidity, saturation, dew point, enthalpy, specific volume
4. How to locate an air state from two independent properties
5. Dew-point reading method and condensation significance
6. Process-direction quick reference
7. Cooling-coil worked example: Point A entering air, Point B leaving air
8. Apparatus Dew Point (Point C), bypass factor and contact factor
9. Condensate and total cooling calculations
10. Outdoor-air / return-air / mixed-air analysis
11. FCU, AHU, ERV, load-calculation and commissioning applications
12. Common mistakes and engineering cautions
13. Interactive PEWDB psychrometric module requirements
14. Source register and references

## Worked cooling-coil state points
- Point A: 80°F DB, 50% RH; W ≈ 0.01092 lb/lb dry air (76.5 grains/lb); h ≈ 31.18 Btu/lb dry air; Tdp ≈ 59.7°F.
- Point B: 55°F DB, 90% RH; W ≈ 0.00826 lb/lb dry air (57.8 grains/lb); h ≈ 22.17 Btu/lb dry air; Tdp ≈ 52.1°F.
- Point C / ADP: extension of A-B to saturation curve; ADP ≈ 50.5°F.
- Bypass factor: BF = (T_leaving - T_ADP)/(T_entering - T_ADP) ≈ 0.15.
- Contact factor: CF = 1 - BF ≈ 0.85.

## Example at 1,000 cfm
- Estimated dry-air flow ≈ 72.2 lb/min at Point A.
- Condensate ≈ 11.5 lb/h ≈ 1.38 gal/h.
- Total cooling ≈ 39,000 Btu/h ≈ 3.25 refrigeration tons.

## Mixed-air example
- OA: 95°F DB, 45% RH.
- RA: 75°F DB, 50% RH.
- 20% OA + 80% RA by dry-air mass gives MA ≈ 79.0°F DB and W ≈ 74.0 grains/lb.

## Interactive implementation targets
The PEWDB module should support DB+RH, DB+WB, DB+DP and other valid input pairs; automatic calculation of psychrometric properties; plotting of state points and process lines; sensible/latent/total loads; SHR; condensate; ADP/BF/CF; mixed-air states; OA → ERV → RA → MA → coil → supply → room sequences; I-P/SI units; pressure/altitude adjustment; warnings; source trace; and report export.

## Sources
- ASHRAE Handbook - Fundamentals (2025), Chapter 1: Psychrometrics.
- ASHRAE Terminology - apparatus dew point and bypass factor.
- ASHRAE Psychrometrics resources and Psychrometric Chart App.
- ASHRAE air-cooling and dehumidifying coil guidance.

**Copyright note:** The PEWDB diagrams are original instructional schematics and are not reproductions of ASHRAE psychrometric charts.