Compressor — ARI 540 and ASHRAE 32 / 46 rating reference

Use these six manufacturer catalogue rating conventions to read compressor data. They describe test conditions, not an automatic capacity calculation or recommended system settings. ARI is the older organization name; AHRI publishes the current 540 standard. This table is not a claim that every edition of AHRI 540 prescribes these points.

Nominal catalogue temperatures; paired units are rounded.
Rating convention / applicationEvaporating Te · °C / °FCondensing Tc · °C / °FReturn gas · °C / °FLiquid · °C / °FTest ambient · °C / °FSource / basis
ARI 540 LBP−23.3 / −1048.9 / 1204.4 / 4048.9 / 12035 / 95Embraco; zero subcooling
ARI 540 MBP−6.7 / 2048.9 / 1204.4 / 4048.9 / 12035 / 95Embraco; zero subcooling; check OEM convention
ARI 540 HBP7.2 / 4554.4 / 13018.3 / 6546.1 / 11535 / 95Embraco; liquid = Tc − 8.3 K
ASHRAE 32 LBP−23.3 / −1054.4 / 13032.2 / 9032.2 / 9032.2 / 90Tecumseh; Secop corroborates rating point
ASHRAE 46 MBP−6.7 / 2054.4 / 13035 / 9546.1 / 11535 / 95Tecumseh + Secop MBP point
ASHRAE 46 HBP7.2 / 4554.4 / 13035 / 9546.1 / 11535 / 95Tecumseh + Secop HBP point

How to choose the matching row

LBP — low back pressure: commonly freezer and other low evaporating-temperature duties. MBP — medium back pressure: commonly medium-temperature refrigeration, such as coolers. HBP — high back pressure: higher evaporating-temperature duties, such as some beverage cooling and air-conditioning applications. These are application families; their ranges overlap and the model's approved operating envelope governs. They are not cabinet temperatures or numeric pressure ratings.

Choose the row named in the manufacturer's report, then compare every temperature. ASHRAE 32 and ASHRAE 46 are catalogue shorthand associated with liquid-temperature conventions, not references to ASHRAE Standard 32 or Standard 46. A catalogue may group MBP/HBP at a different evaporating point: for example, the Embraco source groups its ASHRAE MBP/HBP point at 7.2°C. The separate −6.7°C MBP row here follows the Tecumseh/Secop sources.

What each temperature means

For a consistent saturation basis, suction superheat = RGT − Te and liquid subcooling = Tc − Tliquid. Temperature differences use K (or °C difference), not absolute °C conversion. For blends, follow the OEM's dew/bubble or mean-temperature convention; do not mix conventions. °F = °C × 1.8 + 32. Fahrenheit entries show nominal customary rating points, so small rounding differences are normal.

Using this with compressor selection

  1. Record the refrigerant, exact compressor model, rating report/date, voltage, frequency, speed and required compressor cooling.
  2. Match Te, Tc, return-gas and liquid temperatures to the report. A similar label alone is insufficient: OEMs can publish different conditions.
  3. Obtain cooling capacity and electrical input at those same conditions from the OEM map or selection software. These temperatures alone cannot determine either value.
  4. Compare capacity against the calculated load; check the entire operating envelope and starting/operating limits separately.

Efficiency: COP = cooling capacity (W) ÷ electrical input (W). EER in Btu/(W·h) = 3.41214 × COP. Do not compare EER/COP from different rating points, confuse EER with seasonal SEER, or use a fixed ratio to convert capacity between ARI and ASHRAE ratings. Use the Designer's electrical-input / COP / EER dropdown with matched OEM values.

Sources and review

Reviewed September 20, 2026. Legacy catalogue conditions are preserved as reference values; confirm the current model datasheet and applicable standard edition.