Calculation methods: cooling capacity, condenser heat rejection, compressor power and COP →
How to use
- Select the actual fluid or predefined mixture. Search also recognizes R290 (propane), R600a (isobutane), R717 (ammonia), R744 (CO₂) and R718 (water).
- Enter absolute pressure, not gauge pressure. Metric uses kPa abs; imperial uses psia. Absolute pressure = gauge pressure + local atmospheric pressure, in the same units.
- For superheat use vapor dew temperature; for subcooling use liquid bubble temperature. A temperature difference of 1 K equals 1°C or 1.8°F. Absolute temperature conversion also includes the 32°F offset.
- Vapor temperature + superheat: enter the actual vapor temperature and a nonnegative superheat difference. Dew-point temperature = vapor temperature − superheat. CoolProp calculates the dew-point pressure, then vapor properties at that pressure and actual temperature. For example, 25°C vapor − 5 K superheat gives a 20°C dew point (77°F − 9°F difference = 68°F). The inferred pressure assumes equilibrium for the selected fluid/composition; it is not a pressure measurement. Zero superheat returns saturated vapor. Conditions outside the saturation/model range return an error.
- Liquid temperature + subcooling: enter the actual liquid temperature and a nonnegative subcooling difference. Bubble-point temperature = liquid temperature + subcooling. CoolProp calculates the bubble-point pressure, then the liquid properties at that pressure and actual temperature. For example, 25°C liquid + 5 K subcooling gives a 30°C bubble point (77°F + 9°F difference = 86°F). The inferred pressure assumes equilibrium for the selected fluid/composition; it is not a pressure measurement. Zero subcooling returns saturated liquid. Conditions outside the saturation/model range return an error.
- For saturation, liquid quality is Q=0 and vapor quality is Q=1. For blends, at fixed pressure their temperatures can differ; at fixed temperature their pressures can differ.
- Measured P/T near saturation may be ambiguous. Use a saturation option rather than forcing a phase. Above the critical region there may be no saturation temperature and no conventional superheat/subcooling.
Accuracy and coverage
Direct CoolProp HEOS equations of state, with no fitted lookup tables or ideal-gas substitution. Both web editions use the same bundled engine. All pure/pseudo-pure fluids and predefined mixtures listed by this engine are offered; some listed mixtures lack supported interaction data or fail at particular conditions. These return an explicit error. A listed fluid is not an approval for refrigeration service.
Accuracy depends on the fluid model, mixture composition and operating range. This is not a claim that HEOS is the most accurate model for every refrigerant. Licensed NIST REFPROP can offer different or additional models; it is not included here. No guessed composition or fallback refrigerant is used. Compare manufacturer ratings with matching dew/bubble conventions and reference states.
Enthalpy and entropy use CoolProp's default reference state. Compare differences using the same model. Specific heat and transport properties may be unavailable or singular near saturation/critical conditions; unavailable values are shown explicitly. The tool does not predict two-phase effective viscosity or heat-transfer coefficients.
CoolProp calculation and saturation documentation · Mixture model limitations
Runtime provenance: CoolProp 7.2.1dev WebAssembly engine supplied with your DX System Design Calculator v1.9.18. This version is shown for reproducibility; newer releases can contain different fluid models.
Refrigerant properties calculator — user manual and formulas
This manual describes the seven calculation options in this calculator. Select the correct refrigerant or predefined mixture first. A temperature difference alone does not define a state: superheat alone and subcooling alone cannot determine pressure or other properties.
| Symbol | Meaning and how to obtain it |
| P | Absolute refrigerant pressure at the point being evaluated. Use a pressure measurement or an explicitly assumed design value. |
| T | Actual refrigerant temperature at that same point. For liquid use liquid-line temperature; for vapor use vapor-line temperature. It is not ambient air temperature. |
| Tdew | Saturated vapor / dew-point temperature at P for the selected fluid. |
| Tbubble | Saturated liquid / bubble-point temperature at P for the selected fluid. |
| SH | Superheat: actual vapor temperature above the dew temperature, expressed as a temperature difference. |
| SC | Subcooling: bubble temperature above the actual liquid temperature, expressed as a temperature difference. |
| Q | CoolProp vapor-quality input. This calculator uses only the endpoints Q=0 (saturated liquid) and Q=1 (saturated vapor). Q is not cooling capacity. |
| F | The selected fluid model, including the predefined composition when a mixture is selected. |
Use pressure and temperature from the same location. Pressure loss between a compressor and an evaporator, for example, can change the saturation temperature and therefore the calculated superheat.
2. What to select in each calculation option
Notation: Tdew(P,F) and Tbubble(P,F) mean saturation temperatures obtained from the fluid model. Pdew(T,F) and Pbubble(T,F) mean the corresponding saturation pressures. These are model evaluations, not multiplication.
| Dropdown option | Required inputs | Formula and calculation | When to use it |
| Saturated at pressure | F and P | Liquid: T = Tbubble(P,F), Q=0. Vapor: T = Tdew(P,F), Q=1. Evaluate both endpoint property sets at the entered pressure. | Find boiling/condensing endpoints from a known pressure. |
| Saturated at temperature | F and saturation T | Liquid: P = Pbubble(T,F), Q=0. Vapor: P = Pdew(T,F), Q=1. Evaluate both endpoint property sets at the entered temperature. | Find saturation pressures. This input is a saturation temperature, not a superheated or subcooled line temperature. |
| Superheated: pressure + superheat | F, P, SH | Tdew = Tdew(P,F). T = Tdew + SH. Evaluate vapor properties at P and T. | Known pressure plus measured or design superheat. A design SH yields an assumed state. |
| Superheated: vapor temperature + superheat | F, actual vapor T, SH | Tdew = T − SH. P = Pdew(Tdew,F). Evaluate vapor properties at the inferred P and actual T. | Infer pressure when actual temperature and superheat are both known. SH is normally derived from a pressure measurement; this mode does not provide an independent pressure check. |
| Subcooled: pressure + subcooling | F, P, SC | Tbubble = Tbubble(P,F). T = Tbubble − SC. Evaluate liquid properties at P and T. | Known liquid pressure plus measured or design subcooling. |
| Subcooled: liquid temperature + subcooling | F, actual liquid T, SC | Tbubble = T + SC. P = Pbubble(Tbubble,F). Evaluate liquid properties at the inferred P and actual T. | Infer liquid pressure. An assumed SC produces an assumed pressure, not a measurement. |
| Measured pressure + temperature | F, P, actual T | Evaluate properties directly at P,T. Where saturation exists: SH = T − Tdew(P,F); SC = Tbubble(P,F) − T. Only nonnegative SH/SC values are displayed. | Preferred when both pressure and temperature are measured. Interpret SH for vapor and SC for liquid; the displayed differences alone are not a phase certification. |
Zero SH or SC: the calculator uses the appropriate saturated endpoint directly, avoiding an ambiguous pressure/temperature call on the saturation boundary.
Blends: use dew for superheat and bubble for subcooling. At a fixed pressure the two temperatures can differ (temperature glide). At fixed temperature, the two saturation pressures can differ. The two rows in “Saturated at temperature” therefore need not describe one common-pressure process.
3. Worked examples
Superheated R134a: actual vapor T = 25°C and SH = 5 K. Tdew = 25 − 5 = 20°C. The bundled engine gives P ≈ 571.707 kPa absolute. The final property state is 25°C at that pressure, not 20°C. In imperial units: actual T = 77°F, SH = 9°F difference, dew = 68°F.
Subcooled R134a: actual liquid T = 25°C and SC = 5 K. Tbubble = 25 + 5 = 30°C. The bundled engine gives P ≈ 770.196 kPa absolute. The final property state is 25°C at that pressure. In imperial units: actual T = 77°F, SC = 9°F difference, bubble = 86°F.
4. How the reported properties are calculated
The application performs the temperature-difference arithmetic above and the conversions below. It asks the bundled CoolProp HEOS engine for thermodynamic and transport properties at the resulting state. It does not estimate enthalpy from superheat alone or use a constant specific heat approximation.
| Output | Meaning / relationship | Calculation used |
| Temperature T and pressure P | State temperature and absolute pressure. | Returned by the engine for the selected input pair. |
| Density ρ | Mass per volume: ρ = m/V. | CoolProp Dmass at the state. |
| Specific volume v | Volume per mass. | v = 1/ρ, calculated by the application. |
| Specific enthalpy h | Energy per mass including pressure-volume contribution: h = u + Pv, with P in Pa and v in m³/kg for J/kg. u is specific internal energy. | CoolProp Hmass; the application does not separately evaluate u + Pv. |
| Specific entropy s | Thermodynamic state property. For an internally reversible change, ds = δqrev/T, with absolute T and heat per unit mass. | CoolProp Smass, not a heat-input calculation. |
| Isobaric specific heat cp | Local enthalpy change with temperature at constant pressure: cp = (∂h/∂T)P, for a single phase. | CoolProp Cpmass. It varies with state; do not treat it as a constant across phase change. |
| Dynamic viscosity μ | Resistance to shear flow. | CoolProp VISCOSITY using the available fluid transport model. |
| Thermal conductivity λ | Ability to conduct heat. | CoolProp CONDUCTIVITY using the available fluid transport model. |
Engine call mapping: a state uses the pair (P,T), (P,Q), or (T,Q). Pressure uses Pa and temperature uses kelvin inside the engine. Saturation inversion uses Q=1 for dew or Q=0 for bubble. The fluid identifier is HEOS:: followed by the selected name. Fluid-specific equation-of-state coefficients, mixture interaction parameters and transport correlations reside inside CoolProp; they are not a single universal formula and are not reproduced here. Follow the fluid references in the official documentation for those model details.
Enthalpy and entropy depend on reference-state conventions. This tool retains the engine default. Compare energy and entropy differences using the same refrigerant, composition, model and reference convention. This calculator does not calculate compressor capacity, refrigerant mass flow, COP or EER.
5. All unit-conversion formulas used
Absolute pressure = gauge pressure + local atmospheric pressure, in matching units. The calculator requires absolute pressure and does not automatically add atmospheric pressure. “psia” means absolute psi; “psig” means gauge psi.
| Conversion | Formula |
| Temperature | TK = T°C + 273.15; T°F = 1.8 × T°C + 32; T°C = (T°F − 32)/1.8. |
| SH / SC differences | ΔT°F = 1.8 × ΔTK; ΔTK = ΔT°F/1.8. A 1 K difference equals a 1°C difference. Do not add 32 to a difference. |
| Pressure | PPa = 1000 × PkPa; PkPa = 6.894757293168361 × Ppsia; reverse by division. |
| Density | ρlbm/ft³ = 0.0624279605761446 × ρkg/m³. |
| Specific volume | vft³/lbm = 16.0184633739601 × vm³/kg. |
| Enthalpy | hkJ/kg = hJ/kg / 1000; hBtu/lbm = 0.429922613929492 × hkJ/kg. |
| Entropy | skJ/(kg·K) = sJ/(kg·K) / 1000; sBtu/(lbm·°R) = 0.238845896627495 × skJ/(kg·K). |
| Specific heat | cp,kJ/(kg·K) = cp,J/(kg·K) / 1000; cp,Btu/(lbm·°R) = 0.000238845896627495 × cp,J/(kg·K). |
| Viscosity | μµPa·s = 1,000,000 × μPa·s; μlbm/(ft·s) = 0.671968975139507 × μPa·s. |
| Conductivity | λBtu/(h·ft·°F) = 0.577789318444591 × λW/(m·K). |
Imperial energy conversions use the International Table Btu (Btu IT). lbm means pound mass, ft means foot, and °R means degree Rankine. Reverse output conversions divide by the listed factor. Switching the unit selector converts existing inputs and results; it does not change the physical state. Changing an input clears the old results until you calculate again.
6. Step-by-step use and export
- Select Metric or Imperial.
- Search for and select the actual refrigerant/model. Confirm the mixture composition matches your application.
- Select the calculation option matching the quantities you know.
- Enter values using the displayed units. For a temperature-plus-difference option, enter the actual line temperature.
- Click Calculate properties. Read the dew/bubble and SH/SC summary above the table.
- Use Export results CSV for the property table in the selected units. The CSV records fluid, engine version and calculation mode; it is not a formatted Word report and does not include every entered input or the full manual.
7. Limits and interpreting errors
- Absolute pressure must be positive; temperature must exceed absolute zero; SH and SC must not be negative.
- The saturation temperature implied by a temperature-plus-difference input must fall inside the selected model’s supported saturation range.
- Above the critical region, conventional saturation-based SH/SC is not defined. A valid single-phase P/T state may still be calculable.
- P/T on saturation may not identify liquid versus vapor. Select a saturation mode. This tool has no general two-phase quality input and does not predict two-phase effective transport properties.
- Unsupported mixture interactions, out-of-range states or solver failures produce an error rather than a guessed result. Unavailable specific heat, viscosity or conductivity is shown as Unavailable.
- Displayed digits are numerical formatting, not an accuracy guarantee. Measurement accuracy, composition and model uncertainty still apply.
8. Model references and version
Manual checked against the calculator implementation on October 17, 2026. Both editions bundle CoolProp 7.2.1dev; the live engine version is shown above the calculator. Current online documentation may describe a newer version.
Official CoolProp interface and saturation reference · Fluid model theory and references · Mixture models