2. Calculate each air state
Use °C, absolute kPa, W in kg/kg dry air, h in kJ/kg dry air. The following equations match the workspace’s psychrometric-core implementation. Do not enter g/kg directly where W is required.
2.1 Saturation vapor pressure pws(T)
Set K = T + 273.15. Calculate ln(pws,Pa), then exponentiate and divide by 1000 for kPa. ln denotes the natural logarithm.
For T ≤ 0.01°C, saturation over ice:
ln(pws,Pa) = −5674.5359/K + 6.3925247 − 0.009677843K + 6.2215701×10⁻⁷K² + 2.0747825×10⁻⁹K³ − 9.484024×10⁻¹³K⁴ + 4.1635019 ln(K)
For T > 0.01°C, saturation over liquid water:
ln(pws,Pa) = −5800.2206/K + 1.3914993 − 0.048640239K + 4.1764768×10⁻⁵K² − 1.4452093×10⁻⁸K³ + 6.5459673 ln(K)
The saturation helper accepts −100 to 200°C; that is not the studio’s complete valid state range. Its current plotter restricts dry bulb to −10 to 50°C and pressure to 60–110 kPa. These are code limits, not an accuracy certification for every possible input. The coefficients follow the ASHRAE-style equations used by the local implementation; PsychroLib provides a cross-reference [A].
2.2 From dry bulb and relative humidity
φ = RH/100
pv = φ pws(T)
W = 0.621945 pv/(P−pv)
Ws(T,P) = 0.621945 pws(T)/(P−pws(T))
pv is water-vapor partial pressure. P and pv must use the same units and P must exceed pv. Ws is saturation humidity ratio where pws<P. For example, W=0.010 means 10 g water/kg dry air, not 1% RH.
2.3 Reverse calculations, dew point and other moisture measures
pv = PW/(0.621945+W)
RH = 100 pv/pws(T)
Find dew/frost point by solving pws(Tdp)=pv.
Specific humidity q = W/(1+W) [kg water/kg moist air]
Degree of saturation = W/Ws (multiply by 100 for %)
Absolute water-vapor density = W/v [kg water/m³]
Degree of saturation is not exactly RH. Dew point is not wet bulb. A zero-vapor state has no finite ordinary dew point; the studio shows unavailable if the inverse falls below its solver range. Below freezing, state clearly whether saturation is over ice or liquid; the studio follows the ice branch.
2.4 From dry bulb and wet bulb
First calculate Ws at Twb and P. For the thermodynamic wet-bulb convention used here:
Twb ≥ 0°C:
W = [(2501−2.326Twb)Ws(Twb,P) − 1.006(T−Twb)] / [2501+1.86T−4.186Twb]
Twb < 0°C:
W = [(2830−0.24Twb)Ws(Twb,P) − 1.006(T−Twb)] / [2830+1.86T−2.1Twb]
To find Twb from T and W, solve the relevant equation iteratively. Normally Tdp ≤ Twb ≤ T. Reject negative W, supersaturation and Twb>T. A wet-bulb sensor needs a correctly wetted wick and adequate aspiration; its reading may require an instrument correction. The studio can report unavailable at the small freezing-convention discontinuity rather than invent a value.
2.5 Enthalpy and its inverse
h = 1.006T + W(2501+1.86T)
T = (h−2501W)/(1.006+1.86W)
W = (h−1.006T)/(2501+1.86T)
1.006 is approximate dry-air specific heat, 1.86 is vapor specific heat, and 2501 kJ/kg is the vapor enthalpy offset at 0°C for this reference convention. W multiplies the water-vapor contribution. Use the same convention at both states and for condensate correction. These are ideal-mixture engineering relations, not the full real-humid-air formulation in CoolProp HAPropsSI. That API uses pressure and two independent state properties, with units explicitly documented [B].
2.6 Specific volume, density and mass flow
v = 0.287042(T+273.15)(1+1.607858W)/P [m³/kg dry air]
ρda = 1/v; ρmoist = (1+W)/v
ṁda = V̇actual/v; ṁmoist = ṁda(1+W)
The 0.287042 constant uses kPa in the denominator. Dry-air mass flow stays constant across a leak-free coil, although volume flow changes. If flow is specified at standard conditions, use its stated standard specific volume to obtain mass flow first.
3. Cooling capacity, SHR and condensate
Subscripts i and o mean entering and leaving the selected boundary. Positive values below mean cooling and moisture removal.
Qt,air = ṁda(hi−ho)
Wavg = (Wi+Wo)/2; Tavg = (Ti+To)/2
Qs = ṁda(1.006+1.86Wavg)(Ti−To)
Ql = Qt,air−Qs = ṁda(2501+1.86Tavg)(Wi−Wo)
SHR = Qs/Qt,air; latent fraction = 1−SHR
These formulas yield kW. This average-W sensible/latent split is the studio’s convention; it adds exactly to its ideal-mixture enthalpy difference. Other programs may use entering or leaving W for the split and report a slightly different SHR. Document the convention. SHR is undefined when total cooling is zero. Pure sensible cooling at constant W has SHR≈1. Typical cooling plus dehumidification has 0≤SHR≤1; other processes can produce values outside that range and should not be forced into it.
ṁcond = ṁda(Wi−Wo) [kg/s]
Condensate kg/h = 3600 ṁcond
Qcoil = Qt,air − ṁcond hliquid,drain
For liquid drain water above freezing: hliquid,drain ≈ 4.186 Tdrain [kJ/kg]
The studio reports condensate only for positive moisture removal; a negative difference is moisture addition. Qcoil includes condensate leaving the boundary; Qt,air is the commonly reported air enthalpy difference. Do not mix a condensate-corrected denominator with the uncorrected SHR definition without stating it. Frost formation, ice melting, droplet carryover and transient storage require additional mass/energy terms.
Gross/net capacity and coil versus room SHR
For a downstream fan that adds heat to supply air, net delivered cooling ≈ gross coil cooling − fan heat to air − downstream duct heat gain. Do not subtract these again if the temperature/enthalpy measurements already include them. Fan temperature rise is approximately Qfan,to-air/[ṁda(1.006+1.86W)].
Room SHR = room sensible load/(room sensible+room latent load). Coil SHR includes the actual coil inlet mixture and coil outlet conditions, including outdoor-air load and any applicable fan heat. Room SHR and coil SHR generally differ. Manufacturer rated SHR may be gross or net; confirm its definition before comparing.
Airflow required for a load
ṁda,total = Qt,required/(hi−ho)
ṁda,sensible ≈ Qs,required/[(1.006+1.86Wavg)(Ti−To)]
ṁda,moisture = moisture generation rate/(Wi−Wo)
V̇ = ṁda v at the stated flow plane
Use room and supply states for a room balance; use coil-face states for a coil balance. These three requirements must be reconciled with ventilation, coil selection and fan limits; selecting airflow from the sensible load alone can miss humidity control.
4. Bypass factor, contact factor and apparatus dew point
ADP is an equivalent saturated contact state used to model a wet coil; it is not automatically refrigerant evaporating temperature, chilled-water temperature or a directly measured metal-surface temperature. BF is an effective performance parameter, not necessarily a literal fraction of air that physically misses the fins.
Wadp = Ws(Tadp,P); hadp = h(Tadp,Wadp)
BFh = (ho−hadp)/(hi−hadp)
BFw = (Wo−Wadp)/(Wi−Wadp)
BFt = (To−Tadp)/(Ti−Tadp)
CF = 1−BF
For the studio’s ideal bypass/contact mixture, BFh and BFw match. BFt is a closely related approximation and can differ because moist-air heat capacity varies with W. Do not force all three equal. A large discrepancy can indicate inconsistent data, a partially wet coil, reheat, fan heat or an unsuitable model. A conventional valid wet-coil prediction needs 0≤BF≤1, Tadp below entering dew point, and cooling with moisture removal. BF near 0 means strong contact; BF near 1 means little treatment. No universal BF applies to every coil or airflow.
Predict leaving conditions from ADP and BF
Wo = Wadp + BF(Wi−Wadp)
ho = hadp + BF(hi−hadp)
To = (ho−2501Wo)/(1.006+1.86Wo)
Then calculate RHo, vo, Qt, Qs, Ql and condensate using earlier equations.
Infer ADP from measured entering and leaving states
Search for a saturated state below leaving dry bulb and below entering dew point that satisfies BFh=BFw. Numerically solve:
(ho−h(Tadp,Ws(Tadp,P)))/(hi−h(Tadp,Ws(Tadp,P)))
− (Wo−Ws(Tadp,P))/(Wi−Ws(Tadp,P)) = 0
Check denominators and select a physically valid root with BF between 0 and 1. This is the extension of the process line to saturation in h–W space. If no plausible root exists, do not invent ADP; check the data and model. A dry coil with unchanged W cannot use this wet-coil moisture-ratio procedure. For a simple dry heat-exchanger model BF≈exp[−UA/(ṁcp)], but do not transfer that dry-coil UA relation directly to a wet coil. EnergyPlus describes ADP/BF as a coil model tied to rating data and operating conditions [C].
5. Mixing, ventilation, reheat and humidity control
For adiabatic mixing without condensation, use dry-air mass fractions, not automatically volume fractions. Let f=ṁda,outdoor/(ṁda,outdoor+ṁda,return):
Wmix = f Woutdoor +(1−f)Wreturn
hmix = f houtdoor +(1−f)hreturn
Tmix = (hmix−2501Wmix)/(1.006+1.86Wmix)
Outdoor-air total load relative to room ≈ ṁda,outdoor(houtdoor−hroom)
Check the mixed state is not supersaturated. If fog/condensation occurs, include liquid water and latent heat in the balance. Reheat at constant W uses Qreheat=ṁda(1.006+1.86W)(Tafter−Tbefore); RH falls as temperature rises even though no moisture is removed. Required humidification rate is ṁda(Wtarget−Winitial); actual steam/water energy effects require the relevant energy balance.
If “HR” means heat recovery instead of humidity ratio, use a separately labelled effectiveness: εT=(Tsupply,out−Toutdoor)/(Texhaust,in−Toutdoor), and an analogous enthalpy ratio for total recovery, only with the appropriate rated flow configuration and nonzero denominator. This is not coil BF or SHR.
6. Imperial units and shortcuts
Use measured density or specific volume instead of the shortcut constants when conditions differ from their assumptions. Do not use total moist-air mass flow with enthalpy per kg dry air. RH percentages are never substituted for W.
7. Fully worked example
Inputs: inlet 27°C and 50% RH; pressure 101.325 kPa; actual inlet airflow 1.000 m³/s; assumed equivalent ADP 10°C; BF=0.15; drain temperature 10°C. ADP and BF are illustrative design assumptions, not inferred from inlet RH.
Values retain extra digits to make the calculation traceable, not to imply equivalent field accuracy. This example was computed with the current bundled studio implementation.
8. Checks before accepting the result
- Record pressure, airflow basis and both complete air states; retain units and humidity-ratio mass basis.
- For ordinary wet cooling: Tout<Tin, Wout<Win, hout<hin, condensate>0. RHout can still exceed RHin.
- Check Qs+Ql=Qt under the chosen split and independently compare condensate flow if measured.
- Check dry-air conservation: V̇in/vin≈V̇out/vout for a leak-free steady coil.
- Sample representative air across the coil face; a single point can miss stratification. Avoid water droplets on humidity sensors.
- Confirm fan heat, reheat, leaks, duct heat and condensate boundaries before comparing air-side duty with refrigerant- or water-side duty.
- Small enthalpy or humidity differences magnify sensor errors. Numerical agreement using the same inputs is not independent validation.
- Real-gas humid-air models and ideal-mixture equations can differ. Do not mix property references inside one balance.
Sources and method notes
Reviewed October 17, 2026. Formulas and example were checked against the local Psychrometric Studio implementation; the following primary references explain the method families.
- [A] PsychroLib API reference and documented implementation: state inputs, saturation pressure, humidity ratio, enthalpy and volume.
- [B] CoolProp humid-air documentation: real-humid-air formulation and dry-air versus humid-air mass bases. The studio currently uses its own ideal-mixture implementation, not HAPropsSI.
- [C] EnergyPlus engineering reference — coils: ADP/BF, rating data and operating-condition considerations.
- [D] Trane load design calculations: air-side enthalpy/airflow method.