Compressor selection

Turn your cabinet load into a cooling-capacity requirement and prepare a specification for manufacturer selection. Example values are editable. This tool does not search model performance maps.

First: does your load already include a safety factor?

Use that allowance once. A 24-hour average load still needs an available-running-time calculation. A capacity already corrected for runtime does not. Then compare manufacturer cooling capacity at the actual operating conditions—not motor horsepower.

Example: 2 kW average × 1.10 allowance × 24/18 hours = 2.93 kW cooling. If your 2.20 kW already includes the allowance, use 2.20 × 24/18. If 2.93 kW already includes both adjustments, select the “already adjusted” basis and apply neither again.

Compressor rating reference

Open ARI 540 / ASHRAE 32 / ASHRAE 46 reference table

Show the six rating conditions and explanations

Compressor — ARI 540 and ASHRAE 32 / 46 rating reference

Use these six manufacturer catalogue rating conventions to read compressor data. They describe test conditions, not an automatic capacity calculation or recommended system settings. ARI is the older organization name; AHRI publishes the current 540 standard. This table is not a claim that every edition of AHRI 540 prescribes these points.

Nominal catalogue temperatures; paired units are rounded.
Rating convention / applicationEvaporating Te · °C / °FCondensing Tc · °C / °FReturn gas · °C / °FLiquid · °C / °FTest ambient · °C / °FSource / basis
ARI 540 LBP−23.3 / −1048.9 / 1204.4 / 4048.9 / 12035 / 95Embraco; zero subcooling
ARI 540 MBP−6.7 / 2048.9 / 1204.4 / 4048.9 / 12035 / 95Embraco; zero subcooling; check OEM convention
ARI 540 HBP7.2 / 4554.4 / 13018.3 / 6546.1 / 11535 / 95Embraco; liquid = Tc − 8.3 K
ASHRAE 32 LBP−23.3 / −1054.4 / 13032.2 / 9032.2 / 9032.2 / 90Tecumseh; Secop corroborates rating point
ASHRAE 46 MBP−6.7 / 2054.4 / 13035 / 9546.1 / 11535 / 95Tecumseh + Secop MBP point
ASHRAE 46 HBP7.2 / 4554.4 / 13035 / 9546.1 / 11535 / 95Tecumseh + Secop HBP point

How to choose the matching row

LBP — low back pressure: commonly freezer and other low evaporating-temperature duties. MBP — medium back pressure: commonly medium-temperature refrigeration, such as coolers. HBP — high back pressure: higher evaporating-temperature duties, such as some beverage cooling and air-conditioning applications. These are application families; their ranges overlap and the model's approved operating envelope governs. They are not cabinet temperatures or numeric pressure ratings.

Choose the row named in the manufacturer's report, then compare every temperature. ASHRAE 32 and ASHRAE 46 are catalogue shorthand associated with liquid-temperature conventions, not references to ASHRAE Standard 32 or Standard 46. A catalogue may group MBP/HBP at a different evaporating point: for example, the Embraco source groups its ASHRAE MBP/HBP point at 7.2°C. The separate −6.7°C MBP row here follows the Tecumseh/Secop sources.

What each temperature means

  • Te: refrigerant evaporating saturation temperature, not the cabinet air temperature.
  • Tc: refrigerant condensing saturation temperature, not outdoor ambient.
  • Return gas (RGT): suction gas temperature at the compressor rating boundary; it is an absolute temperature, not the amount of superheat.
  • Liquid: liquid refrigerant temperature used in the rating. For the ARI rows above, it is derived from the source's subcooling: Tliquid = Tc − subcooling.
  • Test ambient: air around the compressor during the rating test; it does not set the project's design ambient.

For a consistent saturation basis, suction superheat = RGT − Te and liquid subcooling = Tc − Tliquid. Temperature differences use K (or °C difference), not absolute °C conversion. For blends, follow the OEM's dew/bubble or mean-temperature convention; do not mix conventions. °F = °C × 1.8 + 32. Fahrenheit entries show nominal customary rating points, so small rounding differences are normal.

Using this with compressor selection

  1. Record the refrigerant, exact compressor model, rating report/date, voltage, frequency, speed and required compressor cooling.
  2. Match Te, Tc, return-gas and liquid temperatures to the report. A similar label alone is insufficient: OEMs can publish different conditions.
  3. Obtain cooling capacity and electrical input at those same conditions from the OEM map or selection software. These temperatures alone cannot determine either value.
  4. Compare capacity against the calculated load; check the entire operating envelope and starting/operating limits separately.

Efficiency: COP = cooling capacity (W) ÷ electrical input (W). EER in Btu/(W·h) = 3.41214 × COP. Do not compare EER/COP from different rating points, confuse EER with seasonal SEER, or use a fixed ratio to convert capacity between ARI and ASHRAE ratings. Use the Designer's electrical-input / COP / EER dropdown with matched OEM values.

Sources and review

Reviewed September 20, 2026. Legacy catalogue conditions are preserved as reference values; confirm the current model datasheet and applicable standard edition.

1. Describe your calculated load

Include transmission, infiltration, product cooling/freezing, fans, lights and applicable defrost heat in the load study. Hours must allow for periods without useful cooling, including defrost/drip delays. The independent peak must be the complete coincident duty, on the same allowance basis as the main load. We take the larger requirement; we do not add the same heat twice. A daily-energy check alone does not prove a pull-down deadline.

2. Define the manufacturer rating point

These fields document your selection conditions; they do not recalculate refrigerant properties or change an entered OEM capacity.

3. Optional manufacturer candidate

Complete the inputs and calculate to prepare your selection specification.

Selection steps and research

  1. Establish the complete cabinet load and identify whether the result is daily energy, an average load, a peak duty or an already adjusted selection capacity.
  2. Apply one documented allowance. For daily energy, divide by available cooling hours; for a 24-hour average, multiply by 24/hours. Do not apply either correction twice.
  3. Check product pull-down separately: product energy divided by the allowed cooling time plus simultaneous background gains. Include freezing latent heat when relevant. Evaluate the changing operating conditions with the manufacturer; one steady point cannot prove the full transient.
  4. Set refrigerant, evaporating and condensing conditions. Cabinet air temperature is not evaporating saturation temperature; outdoor ambient is not condensing saturation temperature. Choose heat-exchanger approaches from their design and verify pressure-drop effects. For blends, record the OEM dew/bubble convention.
  5. Obtain OEM cooling capacity and power at the specified temperatures, superheat/return-gas condition, subcooling, voltage, frequency and speed. A packaged condensing unit may use ambient temperature in its selection software. Do not substitute a nominal horsepower rating for cooling capacity.
  6. Check the manufacturer's operating envelope at holding duty, high ambient, start/pull-down and minimum load. Verify discharge temperature, oil return, modulation, cycling limits and the starting method. An oversized fixed-speed compressor can cycle excessively.
  7. Match evaporator, condenser, expansion device and piping. Approximate condenser heat rejection is cooling duty plus compressor input when that input reaches the refrigerant. That extra heat is not added to the cabinet cooling requirement.
  8. Verify electrical ratings, starting current, protection, approved refrigerant/oil, installation limits and applicable local requirements. Validate pull-down, temperature control, defrost and operation with a commissioning test.

Scope: preliminary capacity specification for a single-stage subcritical system with equal duty sharing. Transcritical CO₂, cascade systems and unequal compressor banks need their manufacturer's dedicated selection workflow.

Primary referenceUse
Copeland: sizing and selecting condensing unitsDaily load, running hours and allowance. Its 5–10% allowance and application-specific operating-hour examples are guidance for walk-ins, not universal cabinet settings.
Copeland AE103, sections 12–16Heat-load categories, hourly duty and component balancing; historical fundamentals, not current model ratings.
Danfoss: system design and component selectionApplication conditions, matching components and validating selections with Coolselector2.

Reviewed September 19, 2026. Formulas and decision checks are an engineering synthesis of these references. No model is automatically approved.